Power Transformer Health Assessments
Winding Resistance
The winding resistance test of a transformer serves several crucial purposes:
- Quality Assurance and Type Testing:
- During manufacturing, the winding resistance test ensures that the transformer’s windings have been correctly wound and that there are no short circuits or open circuits.
- It verifies the quality of the transformer before it is put into service.
- Routine Maintenance and Field Testing:
- Regularly testing the winding resistance helps monitor the health of the transformer during its operational life.
- It detects issues such as loose connections, broken conductor strands, or high contact resistance in tap changers and bushings.
- Deviations from expected resistance values can indicate problems that need attention.
- Assessment of Transformer Performance:
- The winding resistance test provides information about the overall condition of the transformer.
- Abnormal resistance values may indicate internal faults or degradation.
- Temperature Correction:
- The winding resistance measurement is used to estimate the winding temperature.
- Knowing the winding temperature is essential for assessing the transformer’s loading capacity and ensuring safe operation.
In summary, the winding resistance test is a fundamental diagnostic tool that helps maintain transformer reliability and prevent unexpected failures.
A winding resistance test for a transformer is essential for assessing the quality and condition of its windings, tap changer connections, and copper losses. Let’s dive into the details of how to perform this test:
- Purpose of the Winding Resistance Test:
- Calculate the I²R lossesin the transformer.
- Determine the winding temperature at the end of the temperature rise test.
- Serve as a benchmark for assessing potential damages in the field.
- Measurement Procedure:
- For star-connected windings, measure the resistance between the line and neutral terminals.
- For star-connected autotransformers, measure the resistance of the HV side between HV and IV terminals, then between IV and neutral.
- For delta-connected windings, measure the resistance between pairs of line terminals. Since individual winding resistance cannot be measured separately in delta connection, calculate the resistance per winding using the formula:
- Resistance per winding = 1.5 × Measured value
- Temperature Considerations:
- Transformer windings are typically immersed in insulation liquid and covered with paper insulation, making it impossible to directly measure the winding temperature during the test.
- An approximation is used to calculate the winding temperature:
- Temperature of winding = Average temperature of insulating oil
- The average oil temperature should be taken 3 to 8 hours after de-energizing the transformer when the difference between top and bottom oil temperatures is less than 5°C.
- Measurement Methods:
- Voltmeter-Ammeter Method:
- Measure resistance using a simple voltmeter and ammeter.
- Caution: Current should not exceed 15% of the rated current of the winding to avoid inaccuracies due to heating.
- Current-Voltage Method:
- Inject DC current into the winding and measure the corresponding voltage drop.
- Apply Ohm’s law (R = V / I) to determine the resistance.
- Voltmeter-Ammeter Method:
Remember to perform the winding resistance test at each tap.
Demagnetization
When a transformer trips off-line, or after applying DC test signals in, for example, a winding resistance test, the transformer core remains magnetized. As this can cause issues for further tests, international standards and guides recommend demagnetization before doing excitation current and SFRA measurements. It is also recommended to perform demagnetization before the transformer is taken into service, thus avoiding unnecessary high in-rush currents.
Demagnetization of a power transformer is a crucial process to maintain its optimal performance and longevity. Over time, transformers can become magnetized due to various factors, such as electrical surges, improper grounding, or even natural phenomena like lightning strikes1. Let’s explore how demagnetization works and the methods used:
- Causes of Remanent Magnetism:
- DC Testing: During winding resistance measurements (typically performed using DC current), the magnetic core becomes magnetized. After the test, the winding is discharged but remains magnetized.
- Taking the Transformer Out of Service: When a transformer is taken out of service, the flux may remain in a non-zero state due to the phase difference between voltage and current.
- Clearing High Fault Currents: Interruption of high short-circuit currents can also lead to magnetization.
- Effects of Remanent Magnetism:
- Incorrect Relay Operation: Remanence can cause protective relays for overloads and internal faults to falsely operate and disconnect the transformer from the electrical system.
- Demagnetization Methods:
- Rated Voltage at Rated Frequency: Applying the rated voltage at the rated frequency can demagnetize the core.
- Reduced Voltage at Reduced Frequency: Alternatively, a reduced voltage at a reduced frequency can be used.
- Factory Demagnetization: Manufacturers often apply nominal voltage at nominal frequency during production2.
Remember that demagnetization helps prevent operational issues and ensures the reliable functioning of power transformers.
Procedure for demagnetizing a transformer:
- AC Voltage Demagnetization:
- Apply an AC voltageat the low-voltage (LV) side of the transformer.
- Simultaneously energize the ab, bc, and ca
- Follow a sequence similar to the no-load test:
- Raise the voltage to 30%of the LV rated value.
- Hold this voltage for 5 minutes.
- Reduce the voltage back to zero.
- Repeat this process 3 to 5 times.
- This method effectively demagnetizes the core and eliminates residual magnetism2.
- Effects of Residual Magnetism:
- Residual magnetism can lead to high inrush currentsduring re-energization, potentially exceeding the nominal current.
- These high currents can cause mechanical stress, incorrect relay operation, and voltage dips in the grid.
- Diagnostic measurements are also affected by residual magnetism, making reliable condition assessment challenging1.
Remember to follow safety protocols and manufacturer guidelines when demagnetizing transformers. Proper demagnetization ensures reliable transformer operation and accurate diagnostic results.
Transformer Turn Ratio (TTR)
The turns ratio test for a power transformer is essential to ensure its optimal performance. Let’s delve into the details of this crucial test:
- Purpose: The turns ratio test determines the ratio of the high voltage winding to all other windings when the transformer is not under load. It is performed on all taps of every winding.
- Procedure:
- Isolate the Equipment: Apply working grounds to all incoming and outgoing cables and disconnect them from the transformer bushing terminals. Ensure sufficient clearance between disconnected cables and switchgear terminals.
- Connect Test Leads:
- Connect the H designated three-phase test lead to the test set’s mating connection marked with an H.
- Connect the X designated three-phase test lead to the test set’s mating connection marked with an X.
- Connect the H1, H2, H3 designated test leads to the corresponding transformer terminals/bushings (H1, H2, H3). If an H0 terminal/bushing exists, connect the H0 test lead.
- Similarly, connect the X1, X2, X3 designated test leads to the corresponding X1, X2, X3 transformer terminals/bushings. If an X0 terminal/bushing exists, connect the X0 test lead.
- Measure Ratios: Perform turns ratio measurements for all tap positions.
- Validate Ratios: Confirm that the measured ratios are within 5%of the calculated ratios.
- Importance: The turns ratio test assesses the condition of the transformer’s windings and core. It helps detect problems related to design, assembly, handling, overloading, fault conditions, or poor maintenance2.
Remember, accurate turns ratio ensures the transformer’s reliability and efficient operation!
Tap Changer Testing & Dynamic Resistance Measurement
The turns ratio test for a power transformer is essential to ensure its optimal performance. Let’s delve into the details of this crucial test:
- Purpose: The turns ratio test determines the ratio of the high voltage winding to all other windings when the transformer is not under load. It is performed on all taps of every winding.
- Procedure:
- Isolate the Equipment: Apply working grounds to all incoming and outgoing cables and disconnect them from the transformer bushing terminals. Ensure sufficient clearance between disconnected cables and switchgear terminals.
- Connect Test Leads:
- Connect the H designated three-phase test lead to the test set’s mating connection marked with an H.
- Connect the X designated three-phase test lead to the test set’s mating connection marked with an X.
- Connect the H1, H2, H3 designated test leads to the corresponding transformer terminals/bushings (H1, H2, H3). If an H0 terminal/bushing exists, connect the H0 test lead.
- Similarly, connect the X1, X2, X3 designated test leads to the corresponding X1, X2, X3 transformer terminals/bushings. If an X0 terminal/bushing exists, connect the X0 test lead.
- Measure Ratios: Perform turns ratio measurements for all tap positions.
- Validate Ratios: Confirm that the measured ratios are within 5%of the calculated ratios.
- Importance: The turns ratio test assesses the condition of the transformer’s windings and core. It helps detect problems related to design, assembly, handling, overloading, fault conditions, or poor maintenance2.
Remember, accurate turns ratio ensures the transformer’s reliability and efficient operation!
Tan Delta / Power Factor Measurements
Tan Delta test (or Dissipation Factor Test) on a transformer assesses the quality and condition of its insulation by measuring the dielectric loss, indicating how much energy is lost as heat, revealing issues like moisture, contamination, or aging that could lead to failure, with a higher value signaling poorer insulation. It works by measuring the phase angle difference between applied voltage and current, comparing it to the ideal 90-degree lag, and helps predict insulation health and transformer lifespan.
Procedure for Transformer Tan Delta Test
Preparation & Safety:
Isolate the transformer from the
power system (de-energize, open isolators).
Wear PPE and follow safety
protocols.
Record ambient temperature &
humidity.
Connections:
Short all terminals of the HV
windings together and LV windings together with jumpers.
Connect the test set’s ground
terminal to the transformer body/earth.
Connect HV lead of test set to the
winding being tested, LV lead to the ‘tan delta’ (TD) tap of the bushing (after
removing its earth connection).
Testing Modes (Common Modes):
UST (Unshielded Shielded Test): Measures
insulation from winding to ground (with bushing’s TD tap).
GST (Guard or Grounded Shielded
Test): Measures insulation between windings (HV to LV).
GSTg (Ground Shielded Guard
Test): Measures insulation between winding and ground, often used for
bushings.
Apply a low-frequency test voltage
(e.g., 10kV) using the test set.
Measure the tan delta value at
different voltage levels (e.g., normal, 1.5x, 2x).
Correct the measured values to a
standard temperature (e.g., 20°C) using correction factors.
Compare results with manufacturer
standards or previous tests to identify insulation deterioration.
it’s important for:
Early Fault Detection: Identifies insulation problems before they cause catastrophic failure.
Moisture Detection: Moisture significantly increases dielectric loss, making it a key indicator.
Aging Assessment: Reveals insulation degradation from normal aging.
Ensures Reliability: Helps maintain safe and reliable transformer operation, preventing costly outages.
